Verifisert av produsent for 2 måneder siden
PC16 7-wall
An EN 12101-2 and VdS certified natural smoke and heat exhaust double flap ventilator which is primarily used in industrial, commercial and municipal buildings.
Suitable for use in industrial, commercial and municipal buildings.
Apollo is an EN 12101-2 and VdS-certified double-flap ventilator designed for efficient smoke and heat exhaust in fire emergencies. Suitable for industrial, commercial, and public buildings, it combines high-quality components, corrosion-resistant aluminium, and EPDM seals for low air permeability. Available in thermally broken, insulated, or single-skin versions with polycarbonate, insulated, or glass flaps.
Features and benefits:
Dimensions:
Base options:
The following base options are available:
Flaps:
The Apollo ventilator flaps have either insulated aluminium panels or various kinds of polycarbonate multi-wall sheets or insulated glass panels and are clamped in frames made of extruded aluminium profiles. The sheets are installed in such a way that thermal expansion is allowed for, and so there is no damage from screws.
The flaps are set at slightly inclined angles, allowing rainwater to drain off, thus preventing them from getting dirty.
The flaps have been subjected to a wide range of tests, e.g. for impact resistance, resistance to hail, acoustic characteristics, and many others.
The following flap variants are available:
Controls:
The Apollo flap ventilator is opened or closed either electrically or pneumatically by two drive units in each case.
The following drives are available:
The drives are designed to exactly match the particular requirements of the project, which results in lower operating and cabling costs.
Thermal performance (U value):
Up to 1.31 W/m²K depending on product variant selected.
Certification and test results:
In accordance with EN 12101-2:
In accordance with EN 1873:
Additional performance classes:
Acoustics:
Farge | Silver Other |
Overflatebehandling | Mill |
Materiale | Steel Aluminium |
Form | Rectangle Square |
Lengde | Bespoke |
Bredde | Bespoke |
Høyde | Bespoke |
Uniclass | |
CAWS | L10/47 Roof ventilators L10/490 Roof ventilators |
SKU Code | PC16 |
Klassifiseringsdata | |
Standard | To BS EN 12101-2. |
Third-party certification | VdS certified. |
Opening type | B. |
Mounting | Roof-mounted. |
Reliability classification | Re 1000. Veiledning for spesifikasjonsvalg: Plus 10 000 cycles for day-to-day ventilation |
Snow load classification | Manufacturer's standard. Veiledning for spesifikasjonsvalg: Variable, up to 6500 N/m². |
Low ambient temperature classification | T (-15). |
Wind load classification | WL 1500. |
Resistance to heat classification | B300 E. |
Arrangement | Flap. |
Dimensions | |
Length | Veiledning fra produsentInsert requirements, 1000–3000 mm (1 mm increments). |
Width | Veiledning for spesifikasjonsvalg: Insert requirements, 1000–2500 mm (1 mm increments). |
Height | Manufacturer's standard. |
Controls | Pneumatic cylinder. 24 V d.c. electric actuators. 230 V a.c. electric actuators. |
Initiation | Automatic initiation device activated by an electrical signal from a remote source and manual initiation. |
Materials | |
Ventilator | |
Frame | Corrosion-resistant aluminium alloy grade 3005 in accordance with EN 573-3. Veiledning for spesifikasjonsvalg: With stainless steel fixings. |
Louvres | As arrangement. |
Glazing | 16 mm Polycarbonate multi-skin sheet, clear. 16 mm Polycarbonate multi-skin sheet, opal. |
Finish | Mill finish. Polyester powder coated. Veiledning for spesifikasjonsvalg: Standard film thickness: 75 µm. |
Colour | Silver. Veiledning for spesifikasjonsvalg: Standard for mill finish. RAL. Veiledning for spesifikasjonsvalg: Many colour options available; consult manufacturer for details and insert requirements. |
Integral upstands | |
Material | Double-skin aluminium (insulated). Single-skin aluminium. Veiledning fra produsentConsult manufacturer for insulation options. |
Finish | To match frame. Mill finish. Polyester powder coated. Veiledning for spesifikasjonsvalg: Standard film thickness: 75 µm. |
Colour | To match frame. Silver. Veiledning for spesifikasjonsvalg: Standard for mill finish. RAL. Veiledning for spesifikasjonsvalg: Many colour options available; consult manufacturer for details and insert requirements. |
Seals | Manufacturer's standard. Veiledning for spesifikasjonsvalg: Rubber; used to reduce air leakage when closed. |
Fixing | Onto curb. Onto glazing. Onto curtain walling. Onto roof sheeting. |
Locking | Double. Failsafe closed. Failsafe open. |
U-value | Manufacturer's standard. Veiledning for spesifikasjonsvalg: Up to 1.31 W/m²K depending on product variant selected. |
Resistance to fire | E. Veiledning for spesifikasjonsvalg: To EN 13501-1. |
Air permeability | Class 3. Veiledning for spesifikasjonsvalg: To EN 12207:2000. |
Sound insulation | 28 dB Rw. |
Materiale | Steel Aluminium |