NBS Source
I'm a manufacturer

Plymouth Community Diagnostic Centre | BAM UK & Ireland

OVERVIEW

Plymouth Community Diagnostic Centre Case Study

This case study explores Raybloc’s role in supporting BAM UK & Ireland on the new Plymouth Community Diagnostic Centre, delivered for University Hospitals Plymouth NHS Trust.

The project brought together BAM UK & Ireland’s construction expertise, the Trust’s commitment to improving diagnostic access, and Raybloc’s specialist radiation shielding knowledge to help create safe, practical and compliant imaging environments within a modern healthcare facility.

The Challenge

Plymouth Community Diagnostic Centre has been developed to provide a wide range of outpatient diagnostic services in a convenient city centre location, including CT, MRI, X-ray, ultrasound and other clinical services.

For this type of project, radiation shielding is not simply a product requirement. It is a critical part of the building’s clinical safety strategy.

The imaging rooms needed to meet the required radiation protection specification while being carefully coordinated with the wider construction programme. This included wall build-ups, door openings, operator screens, internal windows, service penetrations and adjoining construction details.

Because the centre forms part of a major community healthcare development, the shielding package needed to be practical, compliant, durable and fully integrated into the finished clinical environment.

Supporting BAM UK & Ireland with Specialist Radiation Shielding

Raybloc supported BAM UK & Ireland with the radiation shielding requirements for Plymouth CDC, providing technical coordination, manufacture, delivery and installation of key shielding elements.

As part of the process, Raybloc reviewed room drawings and helped plan how key interfaces, junctions and services entering the rooms would be shielded to maintain continuity across controlled areas.

In diagnostic imaging environments, even small gaps or poorly coordinated interfaces can create issues. By delivering a coordinated shielding package, Raybloc helped support BAM UK & Ireland with a practical solution aligned with the project’s construction programme and clinical requirements.

The Solution

Raybloc supplied and installed a package of radiation shielding products for the Plymouth CDC project, supporting diagnostic imaging areas including CT and X-ray environments.

The scope included lead-lined wall panels, lead-lined doorsets, lead-lined internal windows, X-ray operator screens and installation works carried out by Raybloc’s specialist team.

For CT and X-ray areas, Raybloc supplied lead-lined plasterboard panels with Code 3, Code 5 and Code 6 lead equivalence, complete with lead strips to support shielding continuity between board joints.

Raybloc also provided lead-lined doorsets for the imaging rooms, including single and unequal pair doorsets supplied pre-hung with Code 3 and Code 5 lead equivalence. These included laminate door finishes, hardwood primer-painted frames and architraves, heavy-duty lift-off hinges, hardware, vision panels with interstitial blinds and Raybloc flush-mounted two-stage LED warning lights where specified.

In addition, Raybloc supplied lead-lined internal windows and X-ray operator screens with Code 5 lead equivalence, lead glass viewing sections, laminate finishes, worktop provision, PC plinth and storage shelf to support staff protection, visibility and workflow within the imaging environment.

Specifications and Requirements

Wall Shielding, Installation and Assurance

Raybloc® lead-lined plasterboard panels

  • 12.5mm plasterboard, square edged
  • Code 3, Code 5 and Code 6 lead equivalence supplied across CT and X-ray areas
  • Lead-lined wall areas supplied for CT and X-ray room use
  • Supplied complete with lead strips for joint continuity
  • Installation of lead-lined wall panels by Raybloc
  • Service and electrical penetration protection considered within the shielding package
  • 10-year material and workmanship guarantee
  • 10-year radiation shielding warranty on Raybloc-installed products

Lead-Lined Doorsets

Raybloc® lead-lined single and unequal pair doorsets

  • Pre-hung construction
  • Code 3 and Code 5 lead equivalence supplied across X-ray and CT imaging rooms
  • Laminate door finish
  • Hardwood primer-painted frame and architraves
  • Heavy-duty lift-off hinges
  • Locks, handles and flush bolts where specified
  • Door closers to the main leaf where specified
  • Vision panels with interstitial blinds where specified
  • Raybloc flush-mounted LED two-stage warning lights where specified

Internal Windows

Raybloc® lead-lined internal windows for CT Room 1 and CT Room 2

  • Standard lead-lined internal window construction
  • Code 5 lead equivalence, 2.24mm Pb
  • Hardwood primer-painted frame and architraves
  • Structural opening size: 1998mm x 1098mm
  • Lead glass viewing section size: 1898mm x 998mm
  • Designed to provide protected visibility between the CT room and operator/control area

Operator Screens

Raybloc® X-ray operator screens

  • Code 5 lead equivalence, 2.24mm Pb
  • Main and wing panel configuration
  • Lead glass viewing sections
  • White laminate post-formed worktop
  • PC plinth and storage shelf
  • Laminate finish coordinated with project requirements

The Benefits

This project highlights the importance of early coordination between the main contractor, healthcare project team and specialist radiation shielding manufacturer.

By supporting BAM UK & Ireland on the Plymouth CDC project, Raybloc helped deliver shielding solutions that were practical, compliant and suited to the demands of a modern diagnostic healthcare facility.

The project achieved:

  • Radiation shielding support for diagnostic imaging environments
  • Coordinated installation of lead-lined walls, windows, doorsets and operator screens
  • Practical consideration of penetrations and shielding continuity
  • Durable product finishes suited to clinical use
  • Staff protection through integrated operator screen design
  • Warning light integration within the lead-lined doorset package
  • Specialist installation support from Raybloc’s experienced team

Most importantly, the project contributed to the wider purpose of the Plymouth Community Diagnostic Centre: helping provide local people with improved access to vital diagnostic services in a modern, purpose-built environment.

Raybloc is proud to have supported BAM UK & Ireland, University Hospitals Plymouth NHS Trust and the wider project team with specialist shielding solutions for this important facility.

About Raybloc Radiation Protective Products

Community Diagnostic Centres require radiation shielding partners who understand how to support fast-moving healthcare projects without compromising compliance, coordination or long-term performance.

For CDC projects, Raybloc brings together the key elements needed to deliver safe and practical diagnostic imaging environments, including lead-lined doorsets, wall panels, operator screens, internal windows, warning lights, penetration detailing and specialist installation support.

Because CDCs often include multiple imaging rooms within one purpose-built facility, the shielding package must be carefully coordinated with the contractor, design team, RPA requirements, equipment layouts and site programme.

The Plymouth Community Diagnostic Centre project demonstrates why Raybloc remains a trusted partner for CDC developments, supporting main contractors and NHS teams with practical shielding expertise, reliable manufacture, coordinated installation and products designed to protect staff, patients and the wider community.

No featured products in this case study

Contact Raybloc (X-Ray Protection) Ltd by clicking the button below to find out which products were used in this case study.

More inspiration from Raybloc (X-Ray Protection) Ltd

View inspiration
Birmingham Heartlands Hospital

Birmingham Heartlands Hospital

Glan Clwyd Hospital

Glan Clwyd Hospital

Singleton Hospital Swansea

Singleton Hospital Swansea

Wimpole Street Diagnostic Centre, London- Case Study

Wimpole Street Diagnostic Centre, London- Case Study