Verified by manufacturer over a year ago
Water-based intumescent coating system.
A water-based, white, thin film intumescent coating for the protection of internal structural steelwork to C1 and C2 environments.
Features and benefits:
Color | White |
Finish | Smooth matt finish. Guidance for specification option: A compatible top-seal can be applied if a decorative finish is required. Manufacturer guidanceLevel of finish to be approve by the Architect prior to the start of the project. Contact manufacturer for more information. |
Warranty description | Ten years. Guidance for specification option: AS per AS2312 Guidelines. Check with manufacturers data. Manufacturer guidanceIntumescent coating warranty documentation can only be requested prior to commencement of works. Check with manufacturer. |
Uniclass | |
SpecPack | 05100 Structural Steel |
SpeedSpec | 05100 Structural Steel |
System performance | 90/90/90.Guidance for specification option: Specified Fire Resistance Level up to 90/90/90. |
Primer | Intercure 200.Guidance for specification option: 75 Microns dry film thickness (minimum). Manufacturer guidanceApplication in accordance with C1 and C2 environment. Use of alternative primers needs manufacturers' approval prior application. Refer to manufacturers' data sheets and instructions. |
Intumescent base coat | SC803 intumescent coatings.Manufacturer guidanceApplication as per loading schedule. Refer to manufacturers' data sheets and instructions. |
Sealer coat | Interthane 870.Guidance for specification option: Optional/compatible topcoat in 75 Microns dry film thickness (minimum). Refer to manufacturers' data sheets. Manufacturer guidanceUse of alternative topcoats needs manufacturers' approval prior application. Refer to manufacturers' data sheets and instructions. |
Bolt head and nut protection | Intumescent bolt caps.Guidance for specification option: Bolted connections should be suitably protected with fire rated bolt caps (Assessed to AS1530.4). Check with manufacturer for supply. |
Execution | Airless spray.Brush roller.Manufacturer guidanceApplication in accordance with the manufacturer’s instructions, application conditions and product guidelines. AS1851 Guidelines: Annual Inspection and maintenance as required. |
Standard | AS 1530.4 -2014 |
Environmental specifics | Classification C1 and C2. |
Volume solids | 69%, ±3%. |
VOC | 0.5 g/L. |
Viscosity | 300 - 350 Poise. Guidance for specification option: Spindle 6 @ 20 rpm. |
Application temperature | Between +5°C and 35°C Manufacturer guidanceFor detailed product application instructions ang guidelines. Refer to manufacturers' data sheets. |
Shelf life | 12 months. Guidance for specification option: Stored as recommended in original unopened container. Store in secure, dry warehouse conditions between +5°C and 35°C. Refer to manufacturers' data sheets. |
Colour/ Finish | White. Manufacturer guidanceLevel of finish to be approve by the Architect prior to the start of the project. Contact manufacturer for more information. |
Coverage | 1000 g/m². Guidance for specification option: Based on an applied 0.5 mm dry film thickness |
Curing | 0.2 mm. Guidance for specification option: Curing for DFT 0.2 mm at 3 hours for 10°C, 2 hours for 20°C and 1 hour for 30°C. 0.5 mm. Guidance for specification option: Curing for DFT 0.5 mm at 4 hours for 10°C, 3 hours for 20°C and 2 hour for 30°C. 1.0 mm. Guidance for specification option: Curing for DFT 1.0 mm at 6 hours for 10°C, 4 hours for 20°C and 3 hour for 30°C. Manufacturer guidanceRecommended overcoat time is 16 hours. For detailed product application instructions ang guidelines. Refer to manufacturers' data sheets. |
Contains Red List materials | Yes Guidance for specification option: Ultra-low VOC. Contains no substances of very high concern. |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |