NBS Source
I'm a manufacturer
Compare variants

Intumastic HP

Verified by manufacturer over a year ago

HEBEL PANEL 60 Minutes

TBA Firefly Variant:

High pressure exerting intumescent mastic.

Jump to:
+61754114209 Website

Application

Used to seal and close off various services which penetrate directly through core holes in different fire rated substrates or TBA Firefly™ Intubatt® seals.


For specific applications and FRLs achieved please refer to the referenced Compliance Reports. Must be installed in strict accordance with the construction details contained within the Compliance Reports.

Description

TBA Firefly™ Intumastic HP is a high pressure exerting intumescent mastic used to seal and close off various services which penetrate directly through core holes in different fire rated substrates or TBA Firefly™ Intubatt® seals.


Must be installed in strict accordance with the construction details contained within the compliance reports.

General information

Warranty description

25 year

Uniclass

Pr_30_31_68_42 Intumescent puttiesPrimary

NATSPEC National Classification System

0182 Fire-Stopping

SpeedSpec

07810 Fireproofing

SpecPack

07810 Fireproofing

Specification data - Intumescent putties

Material

Intumescent mastic.

Form

Stick form.

Execution

-

Manufacturer guidance

All service penetrations must be treated in strict accordance with the concise construction details contained within the referenced compliance Reports. These Reports meet Specification A2.3 of NCC2016 Amendment 1 (Including prior versions) & Schedule 5 of NCC2019 (Including amendment 1) for determination of an FRL.

Sizes

310 mL.

Guidance for specification option:

Cartridges (25 in a box).

600 mL.

Guidance for specification option:

Sausages (12 in a box).

Certification

Tested in accordance with AS1530.4-2014.

Assessed inaccordance with AS4072.1-2005.

FAS190235 RIR.

Guidance for specification option:

Warringtonfire report.

FAS190236 RIR.

Guidance for specification option:

Warringtonfire report.

FCO-3228 SFA.

Guidance for specification option:

CSIRO report.

Fire resistance

-/60/60.

Fire rating

60 minutes.

Bonding to substrate

Single mesh 75 mm thick walls.

Use

Wall core holes.