NBS Source
I'm a manufacturer

Compare variants

Bare Cross Laminated Timber Floors - Fire Stopping Service Penetrations Through Core Holes
Bare Cross Laminated Timber Floors - Fire Stopping Service Penetrations Through Core Holes
Bare Cross Laminated Timber Floors - Fire Stopping Service Penetrations Through Core Holes

Verified over a year ago

TBA Firefly

Verified over a year ago

TBA Firefly

Verified over a year ago

TBA Firefly
Summary
Fire-stopping various service penetrations through core holes in bare Xlam cross laminated timber floors.
-
-
Application

Suitable for protecting electrical, communications, mechanical, fire and security, plumbing and hydraulic and wet fire service penetrations passing through core holes.

-
-
Description

Bare Cross Laminated Timber Floors - Fire Stopping Service Penetrations Through Core Holes, TBA Firefly™ FRL-/90/90 systems.


Protecting Electrical, Communications, Mechanical, Fire and Security, Plumbing & Hydraulic & Wet Fire, service Penetrations passing through Core Holes in XLAM 60 and 90 Minute Bare CLT 130 mm thick floor system.


All tested in accordance with AS1530.4-2014 and assessed in accordance with AS4072.1-2005 and confirmed in reports from an accredited testing laboratory.

-
-
Warranty description
25 year
-
-

Specification

Fire performance
-
-
-
Fire resistance level
-
-
-
Standard
To AS 1530.4 and AS 4072.1.
-
-
Value
-/90/90., -/60/60.
-
-

Additional properties

InnerDiameter
170 mm.
-
-
OuterDiameter
270 mm.
-
-
Certification
Warringtonfire Report No: FAS190236 RIR.
-
-
Application

Fire stopping penetrations through core holes.

-
-
Substrate